Mi SciELO
Servicios Personalizados
Articulo
Indicadores
- Citado por SciELO
Links relacionados
- Similares en SciELO
Compartir
Ingeniería Energética
versión On-line ISSN 1815-5901
Resumen
LEON VILTRE, Lesyani T; DOS SANTOS NEVES, Francisco de Assis y MIRIAM, Vilaragut Llanes. Analysis and Modeling of Doubly Fed Induction Generators. Energética [online]. 2014, vol.35, n.2, pp. 101-111. ISSN 1815-5901.
One of the variable speed wind turbines most commonly used today is the doubly feed induction generator(DFIG). A control scheme of DFIG is discussed in this paper. The power converter connected to the grid side (bus) is modeled and controlled using voltage vectororiented dq reference frame, whichguarantees that the active power can be controlled by the daxiscurrent component and consequently the DC bus voltage. The qaxis component is forced to be zero in order to ensurethe unitary power factor. Astator flux oriented control in the rotor circuit converter is used.A novel GDSC-PLL method is used in order to achieve an efficient synchronization with the grid.Onthe order hand, this paper presents an analysis about the DFIG (Double Feed Induction Generator) behavior during voltages sags
Palabras clave : doubly fed Induction generators; control system.