<title-group>
<article-title xml:lang="en"><![CDATA[Feasibility evaluation of two solar cooling systems applied to a cuban hotel. Comparative analysis]]></article-title>
<article-title xml:lang="es"><![CDATA[Evaluacion de factibilidad del uso dos sistemas climatización solar aplicado a un hotel cubano. Análisis comparativo]]></article-title>
</title-group>
<contrib-group>
<contrib contrib-type="author">
<name>
<surname><![CDATA[Díaz Torres]]></surname>
<given-names><![CDATA[Yamile]]></given-names>
</name>
<xref ref-type="aff" rid="A01"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname><![CDATA[Valdivia Nodal]]></surname>
<given-names><![CDATA[Yarelis]]></given-names>
</name>
<xref ref-type="aff" rid="A01"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname><![CDATA[Monteagudo Yanes]]></surname>
<given-names><![CDATA[José Pedro]]></given-names>
</name>
<xref ref-type="aff" rid="A01"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname><![CDATA[Miranda Torres]]></surname>
<given-names><![CDATA[Yudit]]></given-names>
</name>
<xref ref-type="aff" rid="A01"/>
</contrib>
</contrib-group>
<aff id="A01">
<institution><![CDATA[,Centre for Studies of Energy and Environment (CEEMA) of the Cienfuegos University  ]]></institution>
<addr-line><![CDATA[ ]]></addr-line>
</aff>
<pub-date pub-type="pub">
<day>00</day>
<month>04</month>
<year>2016</year>
</pub-date>
<pub-date pub-type="epub">
<day>00</day>
<month>04</month>
<year>2016</year>
</pub-date>
<volume>37</volume>
<numero>1</numero>
<fpage>35</fpage>
<lpage>44</lpage>
<copyright-statement/>
<copyright-year/>
<self-uri xlink:href="http://scielo.sld.cu/scielo.php?script=sci_arttext&amp;pid=S1815-59012016000100005&amp;lng=en&amp;nrm=iso"></self-uri><self-uri xlink:href="http://scielo.sld.cu/scielo.php?script=sci_abstract&amp;pid=S1815-59012016000100005&amp;lng=en&amp;nrm=iso"></self-uri><self-uri xlink:href="http://scielo.sld.cu/scielo.php?script=sci_pdf&amp;pid=S1815-59012016000100005&amp;lng=en&amp;nrm=iso"></self-uri><abstract abstract-type="short" xml:lang="en"><p><![CDATA[ABSTRACT The article presents an analysis of technical and economic feasibility of using two configurations of solar cooling in a Cuban hotel. HVAC hybrid schemes are: a cooler of ice water vapor compression (chiller) interconnected in parallel with a smaller capacity chiller, first with a solar-powered absorption cooling system (SACS), and then with a photovoltaic cooling system(PSC). Both were simulated taking into account the weather conditions in the region, thermodynamic calculation methodologies and principles that govern these technologies. The results show that the use of these alternatives contributes to reducing energy consumption and the environmental impact of heating, ventilation and air conditioning systems (HVAC). Economic analysis highlights that PCS is more favorable than the SACS taking into account the cooling cost generation (CCG) but energy assessment indicates that SACS has higher thermal performance for the case study to which it is applied.]]></p></abstract>
<abstract abstract-type="short" xml:lang="es"><p><![CDATA[RESUMEN El artículo presenta un análisis de factibilidad técnica y económica de uso de dos configuraciones de climatización solar en un hotel cubano. Los esquemas de climatización híbridas son: una enfriadora de agua helada de compresión de vapor (chiller) interconectada en paralelo con una enfriadora de absorción asistida con energía solar térmica (SACS, siglas en inglés), y posteriormente con un chiller asistido por un sistema solar fotovoltaico (PSC, siglas en ingles). Ambos fueron simulados teniendo en cuenta las condiciones meteorológicas de la región, metodologías de cálculo y principios termodinámicos que gobiernan estos sistemas. Los resultados muestran que el uso de estas alternativas contribuye a la reducción del consumo energético y el impacto ambiental de los sistemas calefacción, ventilación y aire acondicionado (HVAC, siglas en inglés). El análisis económico resalta que PCS es más favorable que el SACS, teniendo en cuenta el costo de generación de frío (CCG, siglas en inglés) pero la evaluación energética indica que este último posee mayores prestaciones térmicas para el caso de estudio al cual se le aplica.]]></p></abstract>
<kwd-group>
<kwd lng="en"><![CDATA[chiller]]></kwd>
<kwd lng="en"><![CDATA[feasibility analysis]]></kwd>
<kwd lng="en"><![CDATA[photovoltaic cooling system]]></kwd>
<kwd lng="en"><![CDATA[solar-powered absorption cooling system]]></kwd>
<kwd lng="es"><![CDATA[chiller]]></kwd>
<kwd lng="es"><![CDATA[análisis de factibilidad]]></kwd>
<kwd lng="es"><![CDATA[sistema de climatización solar fotovoltaica]]></kwd>
<kwd lng="es"><![CDATA[sistema de climatización solar por absorción]]></kwd>
</kwd-group>
</article-meta>
</front><body><![CDATA[ <p align="right"><font face="Verdana" size="2"><b>APLICACIONES INDUSTRIALES</b>    </font></p>     <p>&nbsp; </p>     <P><b><font face="Verdana" size="4">Feasibility evaluation of two solar cooling systems applied to a cuban hotel. Comparative analysis</font></b>      <p>&nbsp; </p>     <P><b><font face="Verdana" size="3">Evaluacion de factibilidad del uso dos sistemas climatización solar aplicado a un hotel cubano. Análisis comparativo</font></b>      <p>&nbsp; </p>     <p>&nbsp; </p>     <P><font size="2" face="Verdana"><b>Msc. Yamile Díaz Torres, Msc.<strong>Yarelis Valdivia Nodal</strong>, Dr.<strong>Jos&eacute; Pedro Monteagudo Yanes</strong></b><b>, Msc.<strong> Yudit Miranda Torres</strong></b></font>     <p>    <font face="Verdana" size="2">Centre for Studies of Energy and Environment (CEEMA) of the Cienfuegos University</font>     <p>&nbsp;</p>     ]]></body>
<body><![CDATA[<p>&nbsp;</p> <hr>     <P><font face="Verdana" size="2"><b>ABSTRACT</b></font>      <P><font face="Verdana" size="2">The article presents an analysis of technical and economic feasibility of using two configurations of solar cooling in a Cuban hotel. HVAC hybrid schemes are: a cooler of ice water vapor compression (chiller) interconnected in parallel with a smaller capacity chiller, first with a solar-powered  absorption cooling system (SACS), and then with a photovoltaic cooling system(PSC). Both were simulated taking into account the weather conditions in the region, thermodynamic calculation methodologies and principles that govern these technologies. The results show that the use of these alternatives contributes to reducing energy consumption and the environmental impact of heating, ventilation and air conditioning systems (HVAC). Economic analysis highlights that PCS is more favorable than the SACS taking into account the cooling cost generation (CCG) but energy assessment indicates that SACS has higher thermal performance for the case study to which it is applied.</font>     <P><font face="Verdana" size="2"><b>Key words:</b> chiller; feasibility analysis; photovoltaic cooling system; solar-powered absorption cooling system.</font>  <hr>     <P><font face="Verdana" size="2"><b>RESUMEN</b></font>      <P><font face="Verdana" size="2">El artículo presenta un análisis de factibilidad técnica y económica de uso de dos configuraciones de climatización solar en un hotel cubano. Los esquemas de climatización híbridas son: una enfriadora de agua helada de compresión de vapor (chiller) interconectada en paralelo con una enfriadora de absorción asistida con energía solar térmica (SACS, siglas en inglés), y posteriormente con un chiller asistido por un sistema solar fotovoltaico (PSC, siglas en ingles). Ambos fueron simulados teniendo en cuenta las condiciones meteorológicas de la región, metodologías de cálculo y principios termodinámicos que gobiernan estos sistemas. Los resultados muestran que el uso de estas alternativas contribuye a la reducción del consumo energético y el impacto ambiental de los sistemas calefacción, ventilación y aire acondicionado (HVAC, siglas en inglés). El análisis económico resalta que PCS es más favorable que el SACS, teniendo en cuenta el costo de generación de frío (CCG, siglas en inglés) pero la evaluación energética indica que este último posee mayores prestaciones térmicas para el caso de estudio al cual se le aplica.</font>     <P><font face="Verdana" size="2"><b>Palabras clave:</b> chiller; análisis de factibilidad; sistema de climatización solar fotovoltaica; sistema de climatización solar por absorción . </font>  <hr>     <P>&nbsp;</P>     <P>&nbsp;</P>     <P><b><font face="Verdana" size="3">INTRODUCCI&Oacute;N </font></b>      ]]></body>
<body><![CDATA[<P>&nbsp;</P>      <P><font size="2" face="Verdana">Solar  energy could supply all the present and the future energy needs of the world on  continuing basis. This makes it one of the most promising of the unconventional  energy source[1]. </font>     <P><font size="2" face="Verdana"> The  use of solar energy in applications such as refrigeration has become an  attractive solution in view of the energetic sustainability. In this scenario  where it is evident the increased use of fossil fuels for air conditioning of  buildings, solar cooling technology seems to be a promising alternative to  conventional electrical driven units. The main advantage of solar cooling  systems is the coincidence in time between cooling demand from the building and  energy supply in the form of solar irradiance. This implies the reduction of primary  energy consumption and the decrease of global warning impact of HVAC systems.  Absorption refrigeration systems are not yet competitive to mechanical  compression ones. For that reason, research and development activities are  necessary in order to reduce the cost of using solar assisted air conditioning  in buildings. </font>     <p><font size="2" face="Verdana">Solar  cooling literature is rich in papers that assess, develop and optimize a wide  variety of solar thermal cooling options, particularly absorption cooling  systems. Mokhtar et al. proposed a methodology for assessing solar cooling  technologies based on the performance of each solar cooling technology as a  system taking into account cost and performance parameters in addition to  important boundary conditions of weather and cooling demand.[2] Results showed  that large-scale cooling plant options are the most economical. On a smaller  scale, Fresnel concentrators and thin film photovoltaic (PV) cells are the most  economically viable. In terms of overall efficiency however multicrystalline PV  cells with vapor compression chillers were the most efficient option of all.  Solar resource availability is a major factor in determining the most suitable  solar cooling technology for a certain location. </font></p>     <p><font size="2" face="Verdana">Otanicar et al.analyzed a variety of solar cooling schemes and revealed  some keys details regarding the choice of the system taking into account  economically and environmentally aspects: For solar electric cooling system,  the cost is highly dependent on the system coefficient of performance (COP)  when photovoltaic (PV) prices remain at the current levels but when prices are  lowered the impact of COP on cost diminishes.[3] For solar thermal cooling, the  cost of solar collection is much lower as a percentage of the overall cost, but  the cost of the refrigeration system represents a larger percentage of the  total cost. Additionally, the paper reveals that the costs for solar thermal  cooling are not projected to decrease as much as PV cooling over the next 20 years  due to the relatively stable cost of collection and storage. &nbsp;The tourism sector is one of the main  industries in Cuba, also high consumer of electricity, where it is known that  60% of electricity consumption is due to HVAC equipment. In the country using  solar cooling technologies discussed above are not recorded. In this scenario  the real potential of these systems are not known taking into account the  climatic conditions of the region. The objective of this research is to  investigate the thermal performance of the operation of the two schemes solar  cooling, a SACS and a PSC system using mathematical models to predict the  savings in energy and reduction in CO2 emissions. In order to verify the  systems&rsquo; overall performance, the proposed methodologies is implemented for a  hotel facility and the developed model in this study presents a comprehensive  analysis that suits Cuba climate and an economic assessment based on the  commercialized system components which are commonly existed. The last step was  the comparison of both systems in order to find a better solution to apply a  hybrid scheme for a cooling production.</font></p>     <P>&nbsp;</P>     <P><strong><font size="2" face="Verdana">GENERAL  DESCRIPTION OF THE THERMAL COOLING SYSTEM WITHOUT ANY BACKUP</font></strong>     <P><font size="2" face="Verdana">The SACS consists basically of thermal collectors, a hot water storage tank, lithium bromide solution (LiBr)/water simple effect absorption chiller and a cooling tower which is shown schematically in <a href="#f1">figure 1</a>. The systems include domestic hot water (DHW) production. </font>     <P align="center"><img src="/img/revistas/rie/v37n1/f0105116.jpg" width="517" height="294">    <a name="f1" id="f1"></a>      
<P><font size="2" face="Verdana">The  operation of the system described above generates demand and energy charges  which can be assessed using the basic energy balance equations presented by the  mathematical models used by Ghait and Abussita , with key assumptions that  govern this technology: [5] </font> <ol type="i">       ]]></body>
<body><![CDATA[<li><font size="2" face="Verdana">The system is assumed to be under-steady state conditions. </font></li>       <li><font size="2" face="Verdana">All phases are in thermal and mechanical equilibrium. </font></li>       <li><font size="2" face="Verdana">The water temperature in the tank is uniform. </font></li>       <li><font size="2" face="Verdana">Shading of collector absorber plate is negligible</font></li>       <li><font size="2" face="Verdana">Assuming negligible heat losses in piping between collector and the tank </font></li>       <li><font size="2" face="Verdana">Assuming negligible losses between the storage tank and the generator.</font></li>     </ol>  <font size="2" face="Verdana">The useful energy, Qu collected by the thermal  collectors can be determined by the <a href="#e1">equation (1)</a>, describe by Duffie and  Beckman,[6].</font>     <P align="center"><img src="/img/revistas/rie/v37n1/e0105116.gif" width="496" height="33"> <a name="e1" id="e1"></a>      
<P><font size="2" face="Verdana">Where G, (W/m<sup>2</sup>)  is the incident solar radiation intensity; Ac (m<sup>2</sup>) the  area of collectors, &tau; is  the transmissivity coefficient of the glass cover; &alpha; is the absorptance of receiver&rsquo;splate surface; FR  is the heat removal factor; T<sub>c,i</sub> (K) is the inlet fluid temperature;  T<sub>a</sub>, (K) is the ambient temperature; and U<sub>L</sub>,(W/m<sup>2</sup>/K). is  the overall heat transfer coefficients. The useful energy it&rsquo;s given also by  the first thermodynamics law, <a href="#e2">equation (2)</a>.   </font>     <P align="center"><img src="/img/revistas/rie/v37n1/e0205116.gif" width="382" height="30"> <a name="e2" id="e2"></a>      
]]></body>
<body><![CDATA[<P><font size="2" face="Verdana">Where </font><font size="2">&#7745;</font><font size="2" face="Verdana">, (kg/s) is the  mass flow rate of collectors and T<sub>c,o</sub>, (K) is the outlet fluid  temperature. Combining Eqs. (1)&ndash;(2), the water outlet temperature of the  collectors can be expressed as <a href="#e3">equation (3)</a>: </font>     <P align="center"><img src="/img/revistas/rie/v37n1/e0305116.gif" width="546" height="70"> <a name="e3" id="e3"></a>     
<P><font size="2"face="Verdana"><a href="#e3">Equation (3)</a>, can be  used to estimate the collector area required to provide hot water at specified  flow rate and temperature. </font>     <p><font size="2" face="Verdana"><b>Storage tank</b></font></p>       <p><font size="2" face="Verdana">The energy balance of  the storage tank temperature can express by <a href="#e4">equation (4)</a>:</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/e0405116.gif" width="568" height="57"> <a name="e4" id="e4"></a>       
<P><font size="2" face="Verdana">Where C<sub>pw,s</sub>,(kJ/kgK); </font><font size="2">&#7745;</font><font size="2" face="Verdana"><sub>s</sub>, (kg/s)  and Ts(K)are the specific heat of water, mass flow rate and  temperature of water in the storage tank respectively. C<sub>p,t</sub> and </font><font size="2">&#7745;</font><font size="2" face="Verdana">t  are the specific heat and the mass of the empty tank, respectively. UL(W/m<sup>2</sup>/K)  is the overall heat loss coefficient of the tank and As (m<sup>2</sup>) is the  area of the storage tank. Q<sub>g</sub>, (kW) is the energy received by the  generator in the absorption chiller[7].Assuming negligible heat losses in  piping between collector and the tank by guarantee good thermal insulation  implies that Q=Q<sub>u</sub>.</font> <font size="2" face="Verdana">Losses between the generator circuit and the  storage tank are negligible; the amount of heat which is demanded for driving  the refrigeration cycle is obtained by the following <a href="#e5">equation (5)</a>.</font>     <P align="center"><img src="/img/revistas/rie/v37n1/e0505116.gif" width="350" height="38"> <a name="e5" id="e5"></a>     
<P><font size="2" face="Verdana">Where </font><font size="2">&#7745;</font><font size="2" face="Verdana"><sub>g</sub> is  the mass flow rate of water, T<sub>g,i</sub> and T<sub>g,o</sub>, (K) are the  water inlet and outlet temperature of the generator, respectively. The amount  of heat Qs (kW), stored in a tank for a working day, when the water tank  reaches its maximum temperature, can be expressed by the <a href="#e6">equation (6)</a>. </font>     <P align="center"><img src="/img/revistas/rie/v37n1/e0605116.gif" width="393" height="29"> <a name="e6" id="e6"></a>     
]]></body>
<body><![CDATA[<P><font size="2" face="Verdana">T<sub>s,max</sub>  (K) is the water temperature at storage tank. T<sub>f,I</sub> is the inlet  water temperature entering the tank. At night it is vital to assume that  storage tank is cleaned properly for DHW application when air conditioning system  is switched off. </font>     <P><font size="2" face="Verdana"><b>Absorption chiller</b></font>     <p><font size="2" face="Verdana">For the absorption  chiller, the COP can be expressed as <a href="#e7">equation (7)</a>, where Q<sub>c</sub>(kW) is  the amount of cooling energy generated by the chiller&rsquo;s compressor.</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/e0705116.gif" width="224" height="67"> <a name="e7" id="e7"></a>     
<P><font size="2" face="Verdana"><b>Overall thermal model</b></font>       <p><font size="2" face="Verdana">By substituting  <a href="#e4">equations (4)</a> and  <a href="#e1">(1)</a> into <a href="#e7">equation (7)</a> integrating the heat transfer processes  associated with the solar collector, storage tank, and absorption chiller  obtaining the cooling load concerning the systems can be given by <a href="#e8">equation (8)</a>:</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/e0805116.gif" width="579" height="49"> <a name="e8" id="e8"></a>     
<p><font size="2" face="Verdana">This mathematical model  allows a wide range of cooling load, Q<sub>c</sub>, (kW) varying the system  design parameters such as the collecting area, mass flow, as well as choosing  the appropriate optical parameters according solar technology, to meet the  thermal demand chiller Q<sub>g</sub>(kW). The performance of solar cooling  system (COPs) can be given by <a href="#e9">equation (9)</a>. It&acute;s finding by the COP multiplied  by &eta;,  solar array efficiency [8]:</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/e0905116.gif" width="277" height="39"> <a name="e9" id="e9"></a>     
<P>&nbsp;</P>     ]]></body>
<body><![CDATA[<P><font size="3" face="Verdana"><b>GENERAL  DESCRIPTION OF THE PHOTOVOLTAIC COOLING SYSTEM WITHOUT STORAGE</b> </font>    <p><font size="2" face="Verdana">The system is similar to the  conventional system HVAC but the energy demand is covered by the electricity  obtained by PV modules and if required from the public grid. A PCS without  storage typically consists by four basic components: photovoltaic modules, an  inverter circuit and a vapor compression AC unit which is shown schematically  in <a href="#f2">figure 2</a>.</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/f0205116.jpg" width="452" height="267"> <a name="f2" id="f2"></a>     
<p><font size="2"><b><font face="Verdana">Electrical power generation PV array </font></b></font></p>   <font size="2" face="Verdana">For the PV cooling system described above, the  prediction of PV module performance in terms of electrical  power output in the field, is modeled by the expressions presented by Skoplaki  and Payvos. The power output of PV array can be calculated from the  <a href="#e10">equation (10)</a> [9].</font>     <P align="center"><img src="/img/revistas/rie/v37n1/e1005116.gif" width="495" height="60"> <a name="e10" id="e10"></a>     
<p><font size="2" face="Verdana">Where P<sub>max,ref</sub>,  (W) is the nominal electrical power of photovoltaic generator at under  standards conditions (STC), G<sub>T</sub>(W/ m<sup>2</sup>) is a solar  radiation on tilted plane module G<sub>Tref</sub>, is a solar radiation at STC,  equal 1000 W/ m<sup>2</sup>, &gamma; (&ordm;C<sup>-1</sup>)is the temperature factor for powerequal to  -0.045 for crystalline silicon modules. T<sub>c</sub>, (&ordm;C) is the  cell temperature, is calculated using the <a href="#e11">equation (11)</a>, presented Evans [10].</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/e1105116.gif" width="469" height="28"> <a name="e11" id="e11"></a>     
<p><font size="2" face="Verdana">The operation cell  temperature NOCT employed in <a href="#e11">equation (11)</a>, it is common to use it as an  indicator of module temperature. It is an important parameter in module  characterization since it is a reference of how the module will work when  operating in real conditions. Furthermore, in PV system design and simulation  programs, many calculations are based on the determination of module  temperature from ambient temperature and NOCT. T<sub>amb</sub> (&ordm;C) is the  environmental temperature. The traditional linear expression for the PV  electrical efficiency is given by <a href="#e12">equation (12)</a>, presented in [11].</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/e1205116.gif" width="379" height="36"> <a name="e12" id="e12"></a>     
<p><font size="2" face="Verdana">In which &eta;<sub>ref</sub> is the module&rsquo;s electrical efficiency at  the reference temperature T<sub>ref</sub> equal 25&ordm;C, at solar  radiation flux of 1000 W/m<sup>2</sup>.</font></p>     ]]></body>
<body><![CDATA[<p><b><font size="2" face="Verdana">FEASIBILITY  ANALYSIS </font></b></p>       <p><font size="2" face="Verdana">Final total investment  costs determine annual capital cost and therefore have a strong influence in  the economic and financial values such as payback and cost of primary energy.  The payback period is defined as the period of time (i.e. no. of years) required  for the return of investment and can be expressed mathematically by <a href="#e13">equation  (13)</a>.</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/e1305116.gif" width="580" height="23"><a name="e13" id="e13"></a>     
<p><font size="2" face="Verdana">Various author ranked  the solar cooling technologies according to the cooling generation cost (CGC),  expressed in <a href="#e14">equation (14)</a>, [2][12]. CGC takes into account the capital cost of  the solar field, the cooling equipment, the thermal storage, the land and the  problems of supply&ndash;demand mismatch and how performance of the system changes  with conditions. It also includes the costs of annual maintenance throughout  the life time of the plant embedded in the finance parameter &alpha;.</font></p>     <P align="center"><img src="/img/revistas/rie/v37n1/e1405116.gif" width="580" height="89"> <a name="e14" id="e14"></a>     
<P><font size="2" face="Verdana">Where  Capex is the capital cost [$/kWh cooling capacity], &alpha; is the ratio between the capital investment and the  annual fixed payments, M is the annual maintenance cost [% of Capex per year], &Sigma;O is the annual operation cost [$/kW cooling  capacity], FLH is the usable cooling yield expressed as the number of full load  hours per year [h/year]. </font>     <p><font size="2" face="Verdana">The economic assumptions are: </font></p> <ul>       <li><font size="2" face="Verdana">Maintenance is assumed to  be constant throughout the life time of the plant (25 year), it is normally  provided in the contract as a percentage of Capex. Values between 0.5% and 3%  of Capex are reported in the literature for the solar field and the cooling  equipment </font></li>       <li><font size="2" face="Verdana">Operational cost are mainly  dominated by the cost of electricity needed to run the&nbsp; chilled water pump, cooling tower, condenser  water pump, and air handling unit (AHU).Since we  assume that this demand is met by extra PV cells which price is included in Capex,  operational costs are assumed to be zero.</font></li>     </ul> <font size="2" face="Verdana">The number of full load hour is the total amount  of cooling generated by each technology in kWh, normalized by the total  chillers&rsquo; capacity in kW. This number is the same for all cooling technologies.  Assumed that all technologies should satisfy a solar fraction of 75% of the  cooling load. </font>       ]]></body>
<body><![CDATA[<p><b><font size="2" face="Verdana">Meteorological data</font></b></p>     <p><font size="2" face="Verdana">The global radiation and  ambient temperature is shown in <a href="/img/revistas/rie/v37n1/f0305116.jpg">figure 3a</a>. Integrating a total available solar  energy of 6 967MJ is obtained, corresponding to 6.54 kWh/(m<sup>2</sup>day).  For winter day, <a href="/img/revistas/rie/v37n1/f0305116.jpg">figure 3b</a>. The total available energy of 4 653.44 MJ is  obtained, corresponding 5.04 kWh/(m<sup>2</sup>day). Both examples are good  agreement whit historical data for Cuba.</font></p>       
<p><font size="2" face="Verdana">Measurements daters for <a href="/img/revistas/rie/v37n1/f0305116.jpg">figure 3</a>, were taken outside the building of the  meteorological center of Cienfuegos Cuba.     </font>  </p>       
<P>&nbsp;</P>     <p><font size="3" face="Verdana"><b>RESULTS AND DISCUSSION</b></font></p>       <P><font size="2" face="Verdana"><strong>Case study 1: solar-powered absorption cooling system. Energy  performance</strong></font>    <p><font size="2" face="Verdana">The building considered in the study is a hotel with 149 rooms available  for tourism. The main building has a capacity of one hundred thirty six rooms  (136), a block of thirteen (13) cabins located in the pool area. The HVAC  systems of the hotel are two water chillers model, CHAWT-1402-AT-BP-RC-100  C1-VT, with a cooling capacity: 404 kW each, 115 Tons of refrigeration (TR)  chilled water flow GW-70 m<sup>3</sup> / h. Temperature Input / output: 11/6 &deg; C. The  available roof area is 1500 m<sup>2</sup> for the installation of solar  collectors.</font></p>       <p><font size="2" face="Verdana"> This installation is considered as a transit hotel, so during daylight  hours from 10:00 am to 4:00 pm a maximum of 50 TR it&acute;s only need to satisfy  their air conditioning needs on the &uml;areas nobles&uml; circuit that it&rsquo;s compound  of offices, store and administrations departments. To cover the same mixed air  conditioning scheme, which incorporates a solar absorption air conditioning to  existing conventional HVAC systems is proposed.</font></p>       <P><font size="2" face="Verdana">For the SACS system, the key elements are: solar  collector array: 180 (468 m<sup>2</sup>) Flat plane collector EURO-20 AR. The absorption chiller: COGENIE LT-5 with a capacity of 176 kW and COP  equal to 0.69. The Hot water is driven to the generator side at temperature of  85&ordm;C. This SACS was analyzed under the following operating system:  At 08:30 am when the sunshine on the roof reaches about 200-250 W/m<sup>2</sup>,  the primary circuit pump is switched on and circulate water in a closed  circuit, made by the solar field and heat storage tank, gradually raising the  temperature of the fluid until it&acute;s reaches 80&ordm;C. Then hot water is  driven to the generator circuit. The system doesn&rsquo;t use auxiliary heating  system. The main requirement is that the absorption chiller should be  operational at 10:00 am at 60% of its cooling capacity. The system operates  until 16:00 hours (minimum requirement, could be more, depending on  environmental conditions), when comes into operation the conventional system,  because the thermal load in the hotel increases. When it&rsquo;s not needed to heat  or cool the water or is sent through a heat exchanger for DHW, raising water it  to its operating temperature of 60&ordm;C. The heat delivered to the absorption chiller can be calculated by  integrating the product of the flow rate through the chiller with the  temperature drop across the generator. The flow rate through the chiller is  constant. The operation of the chiller is summarized in <a href="/img/revistas/rie/v37n1/f0405116.jpg">figure 4a)</a>, for a  typical summer day and a typical winter day it&acute;s show in <a href="/img/revistas/rie/v37n1/f0405116.jpg">figure 4b)</a>. In the  figure plot shows inlet/outlet temperature of chilled water (CHW), hot water  (HW) &ndash; left axis, and the coefficient of performance of the chiller (COP)-right  axis.</font>       
<P><font size="2" face="Verdana">In a typical summer day the chiller begins operating at 10:00 am, when  39 800 l of water at the set point of 88&ordm;C have been accumulated.  Operation continues for over 6 hours, during this period of time a 7 592.39 MJ  of hot water from the tank is supplied to the chiller. Return chilled water  from the cold air handlers enters the chiller and is cooled approximately  4.5-6.7&ordm;C in standards conditions, the chilled water flow rate is  constant. A total chilled water production of 3 977.9 MJ, corresponding to an  average chiller COP of 0.53 is obtained, slightly lower than the value that can  be calculated using the manufacturer&acute;s technical literature. The instantaneous  COP plotted oscillates between 0.45 and 0.75, the low values corresponding to  peaks in the heat delivered at the generator circuit. </font>       ]]></body>
<body><![CDATA[<p><font size="2" face="Verdana">In a typical winter day, <a href="/img/revistas/rie/v37n1/f0405116.jpg">figure 4b)</a><a href="#f4"></a> the chiller begins operating at  11:00 am, and the operation continues for over 5 hours, the total heat energy  delivered is 3 110.39 MJ and the total chilled water production of 5 000.39 MJ.  The instantaneous COP oscillates between 0.5 -0.8, corresponding to an average  COP of 0.62 a better performance than in summer day. In resume for a whole year  the SACS supplies the cooling requirements of the hotel during 6 hours. The  overall system predict 300 303 kWh of cooling per year.</font></p>   <font size="2" face="Verdana"><b>Case study 2: Photovoltaic cooling system. Energy performance.</b>  </font>       
<p><font size="2" face="Verdana">The proposed system was  implemented for same facilities. The cooling demand of the building could be  covered during 11:00 am until 4:00 pm by a chiller CHAMT-601 with 159 kW  cooling capacities. For this case it&rsquo;s needed a photovoltaic solar arrays of  454 PV modules JAP6 60-245/3BB750 m<sup>2</sup> for produce enough energy to  cover the demand from 10:00 am to 4:00 pm, and 5 inverters SMA TRIPOWER 17 000  TL. <a href="/img/revistas/rie/v37n1/f0505116.jpg">Figure 5</a>, show the theoretical electric power and  electrical efficiency of the PV array evaluated by using <a href="#e10">equation (10)</a> and  <a href="#e12">equation (12)</a>.</font></p>     
<p><font size="2" face="Verdana">In the case of summer  conditions, the chiller CHAMT-60 requires 54.70 kW of compressor input power to  deliver 159.20 kW of unit capacity. These working conditions are reached from  9:30 a.m. until 5:00 pm. The energy delivered by the photovoltaic array is  obtained by integrating the area under the curve shown in the previous figure.  It&acute;s predicts that this system delivers a total of 619 kWh per day during a  typical summer day and 428 kWh in one typical winter day. This will also allow  delivering to the local grid a total of 288 kWh and 154 kWh, respectively. The  PCS system supplies the cooling requirements of the hotel during 6 hours. The  overall system predict 235 356 kWh of cooling per year.</font></p>        <P ><font size="2" face="Verdana"><b>FEASIBILITY COMPARISON OF BOTH SYSTEMS</b>:</font>       <P><font size="2" face="Verdana">The cost of a solar  cooling installation is a direct function of the design of the entire system,  the weather conditions of the region and the choice of technology constantly  developing by changing the relationship between the surface of solar panels and  air conditioning load or volume storage. In the paper the investment costs are  the sums of all the component of each system. The cost of the main components  is calculated by multiplying the size of each component by specific cost shown  in <a href="#t1">table 1</a>. No funding subsidies are included.   </font>     <P align="center"><img src="/img/revistas/rie/v37n1/t0105116.gif" width="522" height="404"><a name="t1" id="t1"></a>     
<P><font size="2" face="Verdana">Compared to conventional HVAC equipment, these systems are expensive.  According to several case studies analyzed, the investment costs of both technologies in a high percentage exceed  operational costs as shown in <a href="#f6">figure 6</a>. It seems an increase of 40% of SACS regarding the PCS. Due to the complexity of the scheme SACS  system some components like additional pumps, cooling towers, thermal  collectors, storage tanks and relevant controllers are pricey. </font>     <P align="center"><img src="/img/revistas/rie/v37n1/f0605116.jpg" width="426" height="356"><a name="f6" id="f6"></a>     
<P><font size="2" face="Verdana">Considering the  energy performance of both schemes plus the costs of these facilities apply the  expression 14 obtained the CGC of SACS and PCS are 13.7 &cent;/kWh and 0.10. &cent;/kWh&nbsp; respectively. The result also showed that  SACS has slightly longer payback period compared to PCS estimated to be 10  years and 6 years in that order. For the SACS systems the savings means 232.7  Tons CO<sub>2 </sub>reductions of carbon emissions, equivalent also to remove 42  cars out of roads or savings 541.11 barrels of crude oil. For the PCS systems,  included the energy delivered to the local grid. Estimated saving represents  307.4 Tons CO<sub>2</sub> the reduction of carbon emissions, removing 56 cars  out of roads and savings 714 barrels of crude oil.</font>     <P>&nbsp;</P>      ]]></body>
<body><![CDATA[<P><font size="3"><strong><font face="Verdana">CONCLUSION</font></strong></font>     <P><font size="2" face="Verdana">In this  paper, the energy and environmental performance of a SACS system and PSC system  were evaluated and both technologies were compared, considering mathematical  models that describe these systems.&nbsp; In summary,  the outcomes of this paper are outlined below: </font> <ul>       <li><font size="2" face="Verdana">SACS system predicts 300 303 kWh/year  cooling. On a typical summer day the system could work a little more than 7  hours, when solar field will reach peak temperatures between 95&ordm;C  and 100&ordm;C. The instantaneous COP oscillates between 0.45 and 0.75  and the low values will correspond to peaks in the heat delivered at the  generator circuit. On a typical winter day, the COP will improve oscillates  between 0.5 -0.8; but the meteorological conditions will allow the system to  work an average of 5 hours. This configurations offer the advantage of the  availability of hot water for HWD.</font></li>       <li><font size="2" face="Verdana">PCS system predicts 235 356 kWh/year  cooling. The energy delivered by the photovoltaic array will be 619 kWh on a  typical summer day and 428 kWh in one typical winter day. This will also permit  delivering to the local grid a total of 288 kWh and 154 kWh respectively, the  system could work an average of 6 hours. The COPs range from 0.4-0.6, low  values it&acute;s caused by low efficiency performance of PV array.</font></li>       <li><font size="2" face="Verdana">Economic results show that the  photovoltaic cooling system is favorable in comparison with the SACS. An  exhaustive sensitive analysis show a strong influence of initial investment  cost on the payback and in the CGC. But energetic comparison indicates that  SACS has more thermal applications.</font></li>     </ul>     <p>&nbsp;</p>     <p><font size="2"><strong><font face="Verdana">RECOMMENDATIONS </font></strong></font></p>  <ul>       <li><font size="2" face="Verdana">It&rsquo;s convenient the study of the use of solar  photovoltaic&ndash;thermal (PVT) collectors. It&rsquo;s a promising technology that was  receiving wide attention. Cooling of the PV modules by the heat transfer fluid  flowing through the PVT collector then leads to an increase in the overall  energy collection and conversion efficiencies of the system. Also with this  collector is obtained thermal energy for hot water applications.&nbsp;&nbsp; </font></li>       <li><font size="2" face="Verdana">A reduction of this cost is necessary to  increase the feasibility of solar driven cooling systems. Further  comprehensive, prompt research and development activities are necessary in Cuba  in order to promote this kind of air  conditioning hybrid system schemes. </font></li>     ]]></body>
<body><![CDATA[</ul>     <P>&nbsp;</P>     <P><b><font face="Verdana" size="3">REFERENCIAS</font></b></P>      <P><font size="2" face="Verdana">1. SRINIVASA KR, R. Low cost solar cooling system.  International journal of Engineering and innovative technology (IJEIT). 2013;4.  ISSN 2277-3754. </font>     <p><font size="2" face="Verdana">2. MOKHTAR MA, M.; BRAUNIGER, S.; AFSHARI, A.;  SGOURIDIS, S.; ARMSTRONG, P.; CHIESA, M. Systematic comprehensive  techno-economic assessment of solar cooling technologies using location-specific  climate data. Applied energy. 2010;87:3766-78. ISSN 0306-2619.</font></p>     <!-- ref --><p><font size="2" face="Verdana">3. OTANICAR TT, R PHELAN P. Prospects for solar  cooling-An economic and environmental assessment. Solar Energy.  2012;86:1287-99.     ISSN 0038-092X.</font></p>     <p><font size="2" face="Verdana">4. Zhai XQQ, M Li Y, Wang RZ. A review for  research and new design options of solar absorption cooling systems. Renewable  and Sustainable Energy Reviews. 2011;15:4416-23. ISSN 1364-0321. </font></p>     <p><font size="2" face="Verdana">[5. GHAIT FA.  Energy analyses of an integrated  solar powered heating and cooling systems in UAE. Energy and Buildings.  2014;70:117-26. ISSN 0378-7788. </font></p>     <p><font size="2" face="Verdana">6. DUFFIE JAB. Solar Engineering of Thermal  Processes. 3a ed. USA: John Wiley &amp; Sons, Inc.; 2006. ISBN 978-0-470-87366-3.  Disponible en: <a href="http://refhub.elservier.com/S0378-778(13)00721-4/sbref008" target="_blank">http://refhub.elservier.com/S0378-778(13)00721-4/sbref008</a>.</font></p>     ]]></body>
<body><![CDATA[<!-- ref --><p><font size="2" face="Verdana">7. J DARKWA J. Theoretical and practical analysis of an inte-grated solar hot water  powered absorption cooling system. Energy. 2012;39:395-402.     ISSN 0360-5442. </font></p>     <!-- ref --><p><font size="2" face="Verdana">[8.  D&Iacute;AZ. Y M, et al. An&aacute;lisis energ&eacute;tico de un sistema h&iacute;brido de  producci&oacute;n de fr&iacute;o. Ingenier&iacute;a Energ&eacute;tica.  2015;36:38-49.     ISSN 1815-5901.</font></p>     <!-- ref --><p><font size="2" face="Verdana">9. Skoplaki E, et al. On the temperature dependence of photovoltaic module  electrical performance: A review of efficiency/power correlations. Solar Energy 2009; 83:614-24.     ISSN 0038-092X. DOI </font></p>     <!-- ref --><p><font size="2" face="Verdana">10. Evans DL, et al. Cost studies on  terrestrial photovoltaic power systems with sunlight concentration. Solar  Energy. 1977;19:255-62.     ISSN 0038-092X. </font></p>     <!-- ref --><p><font size="2" face="Verdana">11. JAN A. New absorption chiller and control  strategy for the solar assisted cooling system at the German Federal  environment agency. International Journal of Refrigeration. 2014;39:48-56.     ISSN  0140-7007. </font></p>     ]]></body>
<body><![CDATA[<!-- ref --><p><font size="2" face="Verdana">12. EICKER U, et al. Economic evaluation of solar thermal and photovoltaic coolingsystems through  simulation: An analysis in three different cities in Europe. Energy and  Buildings. 2014;70:207-23.     ISSN 0378-7788.</font></p>      <P>&nbsp;</P>     <P>&nbsp;</P>     <P><font face="Verdana" size="2">Recibido: Mayo 2015     <br>   Aprobado: Septiembre 2015 </font>     <p>&nbsp;</p>     <p>&nbsp;</p>     <p><font size="2"><font face="Verdana"><em>Yamile Díaz Torres.</em> </font><font face="Verdana" size="2">Eng in Mechanical Engineering in 2004, the Bs. Eng in Industrial engineering in 2011, and the MS degree in Energy Efficiency in 2013, a professor at the Centre for Studies of Energy and Environment (CEEMA) of the Cienfuegos University and a PhD student.</font><font face="Verdana">    e-mail: <a href="mailto:ydtorres@ucf.edu.cu">ydtorres@ucf.edu.cu</a></font></font>       ]]></body>
<back>
<ref-list>
<ref id="B1">
<label>1</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[Srinivasa]]></surname>
<given-names><![CDATA[K]]></given-names>
</name>
<name>
<surname><![CDATA[Rao]]></surname>
<given-names><![CDATA[R]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[Low cost solar cooling system]]></article-title>
<source><![CDATA[International journal of Engineering and innovative technology]]></source>
<year>2013</year>
<volume>4</volume>
</nlm-citation>
</ref>
<ref id="B2">
<label>2</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[MOKHTAR]]></surname>
<given-names><![CDATA[MA]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[Systematic comprehensive techno-economic assessment of solar cooling technologies using location-specific climate data]]></article-title>
<source><![CDATA[Applied energy]]></source>
<year>2010</year>
<volume>87</volume>
<page-range>3766-78</page-range></nlm-citation>
</ref>
<ref id="B3">
<label>3</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[OTANICAR]]></surname>
<given-names><![CDATA[TT]]></given-names>
</name>
<name>
<surname><![CDATA[R PHELAN]]></surname>
<given-names><![CDATA[P]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[Prospects for solar cooling-An economic and environmental assessment]]></article-title>
<source><![CDATA[Solar Energy]]></source>
<year>2012</year>
<volume>86</volume>
<page-range>1287-99</page-range></nlm-citation>
</ref>
<ref id="B4">
<label>4</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[Zhai]]></surname>
<given-names><![CDATA[XQQ]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[Review for research and new design options of solar absorption cooling systems]]></article-title>
<source><![CDATA[Renewable and Sustainable Energy Reviews]]></source>
<year>2011</year>
<volume>15</volume>
<page-range>4416-23</page-range></nlm-citation>
</ref>
<ref id="B5">
<label>5</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[GHAIT FA]]></surname>
<given-names><![CDATA[R]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[Energy analyses of an integrated solar powered heating and cooling systems in UAE]]></article-title>
<source><![CDATA[Energy and Buildings]]></source>
<year>2014</year>
<volume>70</volume>
<page-range>117-26</page-range></nlm-citation>
</ref>
<ref id="B6">
<label>6</label><nlm-citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname><![CDATA[DUFFIE JAB]]></surname>
<given-names><![CDATA[WA]]></given-names>
</name>
</person-group>
<source><![CDATA[Solar Engineering of Thermal Processes.]]></source>
<year>2006</year>
<edition>3ra</edition>
<publisher-loc><![CDATA[USA ]]></publisher-loc>
<publisher-name><![CDATA[John Wiley & Sons Inc]]></publisher-name>
</nlm-citation>
</ref>
<ref id="B7">
<label>7</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[J DARKWA]]></surname>
<given-names><![CDATA[J]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[Theoretical and practical analysis of an inte-grated solar hot water powered absorption cooling system]]></article-title>
<source><![CDATA[Energy]]></source>
<year>2012</year>
<volume>39</volume>
<page-range>395-402</page-range></nlm-citation>
</ref>
<ref id="B8">
<label>8</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[DÍAZ]]></surname>
<given-names><![CDATA[YM]]></given-names>
</name>
</person-group>
<article-title xml:lang="es"><![CDATA[Análisis energético de un sistema híbrido de producción de frío]]></article-title>
<source><![CDATA[Ingeniería Energética]]></source>
<year>2015</year>
<volume>36</volume>
<page-range>38-49</page-range></nlm-citation>
</ref>
<ref id="B9">
<label>9</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[Skoplaki]]></surname>
<given-names><![CDATA[E]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[On the temperature dependence of photovoltaic module electrical performance: A review of efficiency/power correlations]]></article-title>
<source><![CDATA[Solar Energy]]></source>
<year>2009</year>
<volume>83</volume>
<page-range>614-24</page-range></nlm-citation>
</ref>
<ref id="B10">
<label>10</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[Evans]]></surname>
<given-names><![CDATA[DL]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[Cost studies on terrestrial photovoltaic power systems with sunlight concentration]]></article-title>
<source><![CDATA[Solar Energy]]></source>
<year>1977</year>
<volume>19</volume>
<page-range>255-62</page-range></nlm-citation>
</ref>
<ref id="B11">
<label>11</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[JAN]]></surname>
<given-names><![CDATA[A]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[New absorption chiller and control strategy for the solar assisted cooling system at the German Federal environment agency]]></article-title>
<source><![CDATA[International Journal of Refrigeration]]></source>
<year>2014</year>
<volume>39</volume>
<page-range>48-56</page-range></nlm-citation>
</ref>
<ref id="B12">
<label>12</label><nlm-citation citation-type="journal">
<person-group person-group-type="author">
<name>
<surname><![CDATA[Eicker]]></surname>
<given-names><![CDATA[U]]></given-names>
</name>
</person-group>
<article-title xml:lang="en"><![CDATA[Economic evaluation of solar thermal and photovoltaic coolingsystems through simulation: An analysis in three different cities in Europe]]></article-title>
<source><![CDATA[Energy and Buildings]]></source>
<year>2014</year>
<volume>70</volume>
<page-range>207-23</page-range></nlm-citation>
</ref>
</ref-list>
</back>
</article>